General Maintenance in East Windsor Village

Inspected interior and exterior of HVAC unit over leak area. Dismantled HVAC panel doors, unit curb rail, and counter flashing around curb. Located gap between HVAC unit and HVAC curb where weather seal appears to have failed. Located unsealed/ improperly terminated curb flashing beneath trim coil counter flashing. Sealed curb flashing termination and gap using M1 sealant and reapplied counter flashing. Reassembled unit curb rail and HVAC panel doors. Sealed other potential entryways for water on exterior of unit using M1 sealant.